Omron K6CM User Manual page 265

Motor condition
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Item
Output
Output form
Functions
Output rating
EtherNet/IP
Connected device
Communications
type
Modbus TCP
Connected device
Communications
type
*1. Motors other than three-phase induction motors (e.g., synchronous motor, single phase motor, servo motor,
stepping motor) are excluded.
*2. Judgment of comprehensive alarm as a device:
• Comprehensive alarm threshold setting (Warning) setting: A state in which "Critical" does not exist in the
measurement value and "Warning" exists even in even one.
• Threshold (Critical) setting for comprehensive alarm: A state in which at least one of the measurement val-
ues has "Critical".
*3. Each transistor output 1 and 2 can not be set differently.
*4. A self-diagnosis error occurs due to any one of the following reasons: Refer to Section 10 Trouble shooting
when confirming self-diagnosis error.
Mes cpu error
Mes cpu data flash error
Main cpu error
Main cpu data flash error
Input unit error
Ratings
Item
Power supply voltage
Allowable operating voltage range
Power supply frequency range
Power consumption
Startup time at power ON
LCD display
K6CM Motor Condition Monitoring Device User's Manual (N219)
Transistor output (normally closed)
The following 3 outputs
• Transistor output 1: Comprehensive alarm (Warning) output (Output type*3 can be set
to Normally Open or Normally Close)
• Transistor output 2: Comprehensive alarm (Critical) output (Output type *3 can be set
to Normally Open or Normally Close)
• Transistor output 3: Self diagnostic error output*4 (Normally Close fixed. Self-diagno-
sis error occurrence: OFF, self-diagnosis error not occurred: ON)
Contact configuration: NPN open collector
Rated voltage: 24 VDC
Maximum current: 50 mA
Software tool, or EtherNet/IP compatible equipment such as PC, PLC
• CIP message communication: reception of CIP command
• Tag data link: Output only
Modbus TCP compatible equipment such as PC, PLC
Message communication
K6CM-□□MA: 100 to 240 VAC, 50/60 Hz (Alternating current)
K6CM-□□MD: 24 VAC, 50/60 Hz, 24 VDC (Both direct and alternating current)
85% to 110% of the rated power supply voltage
45 to 65 Hz
K6CM-CI2
24 VAC/24 VDC: 3.2 VA/1.7W max.
100 to 240 VAC: 6.1 VA max.
K6CM-VB
24 VAC/24 VDC: 3.8 VA/2.1W max.
100 to 240 VAC: 7.1 VA max.
K6CM-IS
24 VAC/24 VDC: 3.7 VA/2.0W max.
100 to 240 VAC: 6.2 VA max.
10 s or less
Note : This is the time from power-ON until the monitoring start or "- - - -" is dis-
played.
After that, the measurement value is displayed after the sampling time has
elapsed.
7 segment digital display and single light display Character height 14 mm
Specifications
Specifications
Appendices
A
A - 5