Omron K6CM User Manual page 147

Motor condition
Hide thumbs Also See for K6CM:
Table of Contents

Advertisement

Wiring Diagram of the Insulation Resistance Type (K6CM-IS)
 Three-phase Three Wire S-phase Grounded Delta Connection (With Inverter)
R
3 phase
S
voltage
T
fuse
Single phase
power supply
Measurement trigger signal
PLC etc.
Computer,
PLC etc.
LAN
With the above wiring, set 0 for the Circuit topology and 1 for the Using inverter of the K6CM-ISM
Inverter special measurement setting changes according to inverter frequency (finv).
Example) When the commercial frequency f = 50 H
Method (1)
46 Hz
Method (1) (finv ≤ f - 4 Hz, f + 4 Hz ≤ finv)
• Inverter special measurement:
Method (2) (f - 0.2 Hz ≤ finv ≤ f + 0.2 Hz)
• Inverter special measurement:
• Switch the Inverter special measurement to 1 (ON) when the measurement value falls
below 0.5 MΩ. Measurement with higher accuracy will become possible.
Note In the case of f - 4 Hz < finv < f - 0.2 Hz, f + 0.2 Hz < finv <f + 4 Hz
It can not be measured correctly. Do not use the K6CM device.
*1. For details on how to change the setting, refer to 6-2-1 Settings for Each Monitor Type of K6CM devices on
page 6-19 and 6-2-2 Setting Parameters on page 6-23.
K6CM Motor Condition Monitoring Device User's Manual (N219)
Earth
Red and White
1
7
Red
2
8
Black
3
9
Black and White
4
10
DO NOT USE
DO NOT USE
K6CM-ISM
13
Transistor Output 1
14
15
Transistor Output 2
16
EtherNet/IP or
17
Modbus TCP
Transistor Output 3
LAN
18
Can not be
Method (2)
measured.
49.8 Hz
5 Installation and Wiring
Inverter
L1
L2
L3
*1
IRT0
K6CM-ISZ
IRT1
(special
FG
IRT2
ZCT(IRT))
IRT3
*1: According to IEC 60364 TT method
PLC etc.
PLC etc.
PLC etc.
Can not be
measured.
50.2 Hz
54 Hz
Set to 0 (OFF) and start measurement.
Set to 0 (OFF) and start measurement.
Zero phase current transformer
(Part of K6CM-ISZ)
Monitor target
(motor etc.)
*1
.
Method (1)
[Hz]
finv
5 - 27
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

K6cm-ismK6cm-cimK6cm-vbmK6cm-ci2m

Table of Contents