Input variable
of the commu-
nications
instruction
RqPath
Request path
specification
ServiceDat
Data to send
Size
Number of ele-
ments to send
RespService-
Response data
Dat
specification
K6CM Motor Condition Monitoring Device User's Manual (N219)
8 Monitoring and Setting Using the EtherNet/IP Devices
Value to pass to
Specification
input variable
Specified by user
variable indicating
the Request path
Not used (dummy
variable)
UINT#0
Specified by user
variable r variable to
receive response
data
Meaning
Specify a user-defined variable.
Use the data type "_sREQUEST_PATH" corresponding to the
input variable "RqPath". You can use any variable name.
Specify the following.
Class ID, Instance ID, Attribute ID
Example) Degradation level 1 pv: Specify the following.
• ClassID: = 370 hex (meaning "K6CM monitor object")
• InstanceID: = 01 hex (fixed)
• IsAttributeID: = TRUE (meaning to use an attribute ID)
AttributeID: = 6 FHex (meaning degradation level 1 pv)
Since the service code is "read", specify a Dummy variable (any
data type).
Since the service code is "read", specify integer 0 (fixed).
Specify a user-defined variable.
Use the data type "ARRAY [0..10] OF BYTE" corresponding to
the input/output variable "RespServiceDat". You can use any
variable name.
8
8 - 29