Simatic Hmi Addressing - Siemens SINAMICS S120 Function Manual

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

11.2.2.5

SIMATIC HMI addressing

You can use a SIMATIC HMI as a PROFIBUS master (master class 2) to access SINAMICS
directly. With respect to SIMATIC HMI, SINAMICS behaves like a SIMATIC S7. For
accessing drive parameters, the following applies:
● Parameter number = data block number
● Parameter sub-index = bit 0 ... 9 of data block offset
● Drive object number = bit 10 ... 15 of data block offset
Pro Tool and WinCC flexible
The SIMATIC HMI can be configured flexibly with "Pro Tool" or "WinCC flexible".
The following specific settings for drives must be observed when configuration is carried out
with Pro Tool or WinCC flexible.
Controllers: Protocol always "SIMATIC S7 - 300/400"
Table 11- 9
Field
Network parameter profile
Network parameter baud rate
Communication partner address
Communication partner
slot/rack
Table 11- 10 Variables: "General" tab
Field
Name
Controller
Type
Area
DB
(data block number)
DBB, DBW, DBD
(data block offset)
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
Additional parameters
11.2 Communication via PROFIBUS DP
Value
DP
Any
PROFIBUS address of the drive unit
Don't care, 0
Value
Any
Any
Depending on the addressed parameter value,
e.g.:
INT: for integer 16
DINT: for integer 32
WORD: for unsigned 16
REAL: for float
DB
Parameter number
1 ... 65535
Drive object No. and sub-index
bit 15 ... 10: Drive object No. 0 ... 63
bit 9 ... 0: Sub-index 0 ... 1023
or expressed differently
DBW = 1024 * drive object No. + sub-index
Communication
683

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents