r2074 and r2075 enable the source of a slave-to-slave communication relationship to be
verified in the subscriber.
Note
The subscribers do not monitor the existence of an isochronous publisher sign-of-life.
Faults and alarms with PROFIBUS slave-to-slave communication
The alarm A01945 signals that the connection to a least one publisher of the drive device is
missing or has failed. Any interruption to the publisher is also reported by the fault F01946 at
the affected drive object. A failure of the publisher only impacts the respective drive objects.
More detailed information on the messages can be found in the SINAMICS S120/S150 List
Manual.
11.2.5

Messages via diagnostics channels

Messages can be displayed not only via the well-known commissioning tools (STARTER,
SCOUT). After the activation of a diagnostic function, the messages are also transferred to
the higher-level controller via the standardized PROFIdrive fault classes. The messages are
evaluated there or forwarded for convenient display to the corresponding user interfaces
(SIMATIC HMI, TIA Portal, etc.).
In this way, problems or faults can be located immediately regardless of the tool currently
being used, and then corrected immediately.
Also note the general information on the diagnostics channels in Section Diagnostics
channels (Page 670).
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
11.2 Communication via PROFIBUS DP
Communication
705