Communication
11.3 Communication via PROFINET IO
I&M parameter
designation
I&M 3: DESCRIPTOR
I&M 4: SIGNATURE
The I&M data sets 1...4 are stored permanently in parameters p8806...p8809. Significant
properties of these four parameters:
● They can be displayed in the STARTER expert list.
● The SINAMICS "Reset parameter" (p0976 = 1, p0970 = 1) function does not have any
effect on the content of the parameters.
● I&M data sets are not changed when the alternative parameter sets are stored or loaded.
The transfer of parameter sets between a memory card and non-volatile device memory
does not have any effect on the I&M data sets.
Overview of important parameters (see SINAMICS S120/S150 List Manual)
• p8805[0...1]
• p8806[0...53]
• p8807[0...15]
• p8808[0...53]
• r8809[0...53]
754
Format
Size/
Initialization
octets
Visible
54
Space
string
0x20...0x20
Octet
54
Space
string
0x00...0x00
Identification and Maintenance configuration
Identification and Maintenance 1
Identification and Maintenance 2
Identification and Maintenance 3
Identification and Maintenance 4
SINAMICS
Meaning
parameters
p8808[0...53]
Text with any comments or notes.
p8809[0...53]
The parameter can be filled automatically
by the system, in which case it contains a
standard value, namely, a functional check
signature for the change tracking by
Safety Integrated. The check signature
has the following format:
The first four octets (0...3) contain the
content of parameter r9781 index 0:
"SI change monitoring checksum
(Control Unit)".
The second four octets (4...7) contain
the content of parameter r9782 index
0: "SI change monitoring time stamp
(Control Unit)".
The remainder (octets 8...53) contains
zeroes.
Alternatively, a user can enter a user
value from an application and so overwrite
the standard value. Parameter p8805
specifies which value is entered in p8809:
p8805 = 0 standard value entered
p8805 = 1 user value entered
When p8805 = 0 is set, the standard
setting for p8809 is restored again.
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4