CUA32
Setting the temperature measurement and the temperature channels:
● p0600[0...n] = 10 sets the temperature sensing via BICO interconnection.
● p4600[0...n] sets the sensor type for temperature channel 1 (encoder interface).
● p4601[0...n] sets the sensor type for temperature channel 2 (terminal strip).
CU310-2 DP/PN (AC Drive)
Setting the temperature sensing and the temperature channels:
● p0600[0...n] = 10 sets the temperature sensing via BICO interconnection.
● p4600[0...n] sets the sensor type for temperature channel 1 (encoder interface).
● p4601[0...n] sets the sensor type for temperature channel 2 (terminal strip).
9.5.10

Motor with DRIVE-CLiQ

The motor and encoder data are saved as an electronic type plate in a motor equipped with
a DRIVE-CLiQ connection. This data is transferred to the Control Unit when commissioning.
As a consequence, when commissioning this motor type, all of the necessary parameters
are pre-assigned and set automatically. The same is true for the parameters required to
monitor the motor temperature. Other changes are not required.
The default settings for monitoring the motor temperature are:
● p0600 = 1, motor temperature sensor for monitoring via encoder 1
● p0601 = 2, the motor temperature sensor type is a KTY84.
● p0604[0...n] motor temperature alarm threshold
● p0605[0...n] motor temperature fault threshold
● p0606[0...n] motor temperature timer (timer to changeover from an alarm to a fault value).
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
Monitoring and protective functions
9.5 Thermal motor protection