Siemens SINAMICS S120 Function Manual page 379

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Updating the firmware via the Web server to the latest version
1. Update the data on the memory card:
2. The firmware for the DRIVE-CLiQ components is automatically updated. A new reset is
3. POWER ON of the drive unit (Control Unit and all DRIVE-CLiQ components).
Updating the firmware from the memory card to the latest version
1. Replace the memory card:
2. Go online and download the project to the target device, then execute the "Copy RAM to
3. The firmware for the DRIVE-CLiQ components is automatically updated.
4. Wait until the Control Unit has completed the transfer of the new firmware. This is
5. Carry out a POWER ON for the drive unit (Control Unit and all DRIVE-CLiQ components).
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
– Start the Web server (Page 399)
– Transfer the firmware via the Web server to the memory card (Page 375)
After the update of the data on the memory card, the new data is unzipped and checked
automatically. A reset is then triggered.
triggered.
The new data is then duplicated on a backup partition of the memory card, so that in the
event of damage to the data the duplicate can be accessed (see also Protection against
power failure (Page 381)).
After the complete power up, the new firmware version is active in the DRIVE-CLiQ
components and subsequently displayed in the version overview.
– Disconnect the Control Unit from the power supply
– Remove the memory card containing the old firmware version
– Insert the memory card containing the new firmware version
– Power-up the Control Unit again
ROM..." command.
signaled at the diagnostic RDY LED.
After the complete power up, the new firmware version is active in the DRIVE-CLiQ
components and subsequently displayed in the version overview.
7.24 Upgrade the firmware and project
Basic functions
379

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents