Basic functions
7.24 Upgrade the firmware and project
Once the project has been downloaded or automatic configuration has been carried out, the
firmware is automatically upgraded on all the connected DRIVE-CLiQ components. This
upgrades all DRIVE-CLiQ components to the firmware releases that match the memory card.
Update
This operation can take several minutes. This is indicated by the RDY-LED on the
corresponding components flashing green/red and the Control Unit RDY-LED flashing
orange at 0.5 Hz.
Parameter p7827 indicates the progress.
The update has been completed if the RDY-LED on the Control Unit stops to flash at 0.5 Hz.
Once the update process has been completed, the RDY-LED of the respective component
goes into a steady light condition, for which the upgrade has been completed and the new
firmware has been activated. For the components for which the RDY LED flashes green/red
at 2 Hz you must perform a POWER ON to activate the new firmware.
Note
When activating the new firmware, it is possible that a component interrupts cyclic
communication. Communication problems will then occur that you must acknowledge.
For individual components, STARTER dialogs ("Drive Unit" -> "Configuration" -> "Version
Overview") can be used to read the firmware version or start a firmware upgrade manually
for specific components. The versions of the DRIVE-CLiQ components and that of the
Control Unit can also differ. Information can be found in the version overview.
Note
DRIVE-CLiQ components with higher firmware releases are downwards compatible and also
operate with DRIVE-CLiQ components that have lower firmware releases.
374
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4