Siemens SINAMICS S120 Function Manual page 728

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Communication
11.3 Communication via PROFINET IO
Setting criteria for times
● Cycle (T
– T
– T
● T
– Setting the times in T
– T
● Settings and tuning can be done via a tool (e.g. HW Config in SIMATIC S7).
User data integrity
User data integrity is verified in both transfer directions (IO controller <––> IO device) by a
sign-of-life (4-bit counter).
The sign-of-life counters are incremented from 1 to 15 and then start again at 1.
● IO controller sign-of-life
– STW2.12 ... STW2.15 are used as the IO controller sign-of-life.
– The IO controller sign-of-life counter is incremented in each IO controller application
– The number of sign-of-life errors tolerated can be set via p0925.
– p0925 = 65535 deactivates sign-of-life monitoring on the IO device.
– Monitoring
● IO device sign-of-life
– ZSW2.12 ... ZSW2.15 are used as the IO device sign-of-life.
– The IO device sign-of-life counter is incremented in each DC cycle (T
728
)
DC
must be set to the same value for all bus nodes. T
DC
> T
and T
DC
CA_Valid
T
is thus large enough to enable communication with all bus nodes.
DC
and T
IO_Input
IO_Output
time in the position control loop.
> T
+ T
IO_Output
CA_Valid
cycle (T
).
CACF
The IO controller sign-of-life is monitored on the IO device and any sign-of-life errors
are evaluated accordingly.
The maximum number of tolerated IO controller sign-of-life errors in succession can
be set via p0925.
If the number of tolerated sign-of-life errors set in p0925 is exceeded, the response is
as follows:
1. A fault (F01912) is output.
2. The value "0" is output as the IO device sign-of-life.
3. A new synchronization (at least 15 received correct signs-of-life in succession) with
the IO controller sign-of-life is started.
One sign-of-life error can be reset with ten correct signs-of-life in succession.
– Monitoring of the IO device sign-of-life can be implemented in the controller
application.
≧ T
DC
IO_Output
and T
to be as short as possible reduces the dead
IO_Input
IO_Output
IO_Output_MIN
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
is a multiple of SendClock.
DC
).
DC
Drive functions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents