Restoring NVRAM data
With p7775 = 2, the NVRAM data is transferred back from the memory card into the Control
Unit. When restoring you decide which data you require and want to copy.
There are two reasons that necessitate the NVRAM data being restored.
● Replacing the Control Unit.
● Specific restoration of the NVRAM data as it is possible that there are data errors.
When restoring, the Control Unit always searches first for the "PMEMORY.ACX" file. If the
file is available with a valid checksum, then it is loaded.
Replacing the Control Unit:
If a Control Unit has to be replaced, then this is identified by SINAMICS as a result of the
modified Control Unit serial number. After the POWER ON, the NVRAM of the Control Unit is
first deleted. The new NVRAM data is then loaded.
NVRAM restoration:
A specific restoration of the saved NVRAM data is initiated by setting p7775 = 2. The original
file in the NVRAM is first deleted. If the file "PMEMORY.ACX" is available with a valid
checksum, it is loaded to the NVRAM.
The following data is not imported again:
● Control Unit operating hours counter
● Control Unit temperature
● Safety logbook
● Crash diagnostics data
Deleting NVRAM data
With p7775 = 3, the NVRAM data is deleted.
The following data is not deleted:
● Control Unit operating hours counter
● Control Unit temperature
● Safety logbook
● Crash diagnostics data
Note
NVRAM and know-how protection
Know-how protection and write protection apply to parameter p7775. If the parameter should
be readable despite activated protection mechanisms, then p7775 must be placed in the
exception list.
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
Basic information about the drive system
13.6 Data backup
825