Vector control
5.16 Quick magnetization for induction motors
Figure 5-22
Notes
When quick magnetization is selected (p1401.6 = 1), smooth starting is deactivated internally
and alarm A07416 displayed.
When the stator resistance identification function is active (see p0621 "Identification of stator
resistance after restart") is active, quick magnetization is deactivated internally and alarm
A07416 displayed.
The parameter (p1401.6 = 1) does not work when combined with the "flying restart" function
(see p1200), i.e. flying restart is performed without quick magnetization.
236
Quick magnetization characteristics
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
Drive functions