Siemens SINAMICS S120 Function Manual page 283

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Size
Reference modulation
depth
Reference flux
Reference temperature
Reference electrical
angle
Note
Operation of motors in the field-weakening range
If the motors are to be operated in the field-weakening range > 2:1, the value of parameter
p2000 must be set ≤ 1/2 x maximum speed of the drive object.
Scaling for the A_INF drive object
Table 7- 3
Size
Reference frequency
Reference voltage
Reference current
Reference power
Reference modulation
depth
Reference temperature
Reference electrical
angle
Scaling for the S_INF drive object
Table 7- 4
Size
Reference frequency
Reference voltage
Reference current
Reference power
Reference modulation
depth
Reference temperature
Reference electrical
angle
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
Scaling parameter
100% = Maximum output
voltage without overload
100% = Rated motor flux
100% = 100° C
100% = 90°
Scaling for the A_INF drive object
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = r2004
100% = Maximum output
voltage without overload
100% = 100° C
100% = 90°
Scaling for the S_INF drive object
Scaling parameter
100% = p2000
100% = p2001
100% = p2002
100% = r2004
100% = Maximum output
voltage without overload
100% = 100° C
100% = 90°
7.2 Reference parameters/normalizations
Default when commissioning for the first time
-
-
p2006
P2005
Default when commissioning for the first time
p2000 = p0211
p2001 = p0210
p2002 = r0206/p0210/√3
r2004 = r0206
-
p2006
-
Default when commissioning for the first time
p2000 = 50 Hz
p2001 = p0210
p2002 = r0206/p0210/√3
r2004 = r0206
-
p2006
-
Basic functions
283