Siemens SINAMICS S120 Function Manual page 739

Drive functions
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

The STARTER window opens automatically
The project is displayed in the navigation window.
1. In the expert list of the Control Unit, set parameter p8929 = 2.
Figure 11-42 p8929 from the expert list of the Control Unit
2. Configure an infeed and three drives in servo control. We have selected telegram 370 for
Figure 11-43 Telegram overview for PROFIdrive channel IF1
3. Under ".....", add the safety telegrams 30 for the 1st and 3rd drive:
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
the infeed communication, and standard telegrams 1, 2 and 3 for the drives.
– Then click under project "Save and recompile all".
– Click in the navigation window "Communication \ Telegram Configuration".
– In the table, click the drive that you want to monitor with PROFIsafe.
– Click the "Adapt telegram configuration" button and select "Add PROFIsafe".
Figure 11-44 Add the PROFIsafe telegram to the drive
11.3 Communication via PROFINET IO
Communication
739