Restrictions
The following restrictions must be taken into account when a dv/dt filter is used:
● The output frequency is limited to a maximum of 150 Hz.
● Maximum permissible motor cable lengths:
● Further restrictions are contained in the following device manuals:
Commissioning
During commissioning, you must activate the dv/dt filter with p0230 = 2.
Drive functions
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
– Shielded cables: Max. 100 m
– Unshielded cables: Max. 150 m
– SINAMICS S120 AC Drive
– SINAMICS S120 Chassis Power Units
– SINAMICS S120 Liquid Cooled Chassis Power Units
7.7 dv/dt filter compact plus Voltage Peak Limiter
Basic functions
293