Infeed
2.1 Active Infeed
Switching off the Active Line Module
The Active Line Module is switched off by the same procedure used to switch it on, but in the
reverse order. However, there is no pre-charging at switch off.
Switching off the controller with the OFF1 signal is delayed by the time entered in p3490.
This allows the attached drives to be braked in a controlled manner. Before the infeed is
switched off, the drives connected to the DC link should be in pulse inhibit mode.
Control and status messages
Table 2- 2
Active Infeed open-loop control
Signal name
ON/OFF1
OFF2
Enable operation
Disable motor
operation
Inhibit regenerating
Acknowledge fault
Master control by PLC
Table 2- 3
Active Infeed status message
Signal name
Ready to start
Ready
Operation enabled
Fault active
No OFF2 active
Switching on inhibited
Alarm active
Switch-on operation active
Control requested
Pre-charging completed
Line contactor closed
34
Internal control
Binector input
word
STWAE.0
p0840 ON/OFF1
STWAE.1
p0844 1 OFF2 and
p0845 2 OFF2
STWAE.3
p0852 Enable operation
STWAE.5
p3532 Disable motor
operation
STWAE.6
p3533 Inhibit
regenerating
STWAE.7
p2103 1 Acknowledge or
p2104 2 Acknowledge or
p2105 3 Acknowledge
STWAE.10
p0854 Master control by
PLC
Internal status
word
ZSWAE.0
ZSWAE.1
ZSWAE.2
ZSWAE.3
ZSWAE.4
ZSWAE.6
ZSWAE.7
ZSWAE.8
ZSWAE.9
ZSWAE.11
ZSWAE.12
Display of internal
control word
r0898.0
r0898.1
r0898.3
r0898.5
r0898.6
r2138.7
r0898.10
Parameter
PROFIdrive telegram 370
r0899.0
E_ZSW1.0
r0899.1
E_ZSW1.1
r0899.2
E_ZSW1.2
r2139.3
E_ZSW1.3
r0899.4
E_ZSW1.4
r0899.6
E_ZSW1.6
r2139.7
E_ZSW1.7
r0899.8
E_ZSW1.8
r0899.9
E_ZSW1.9
r0899.11
E_ZSW1.11
r0899.12
E_ZSW1.12
Function Manual, (FH1), 04/2014, 6SL3097-4AB00-0BP4
PROFIdrive telegram
370
E_STW1.0
E_STW1.1
E_STW1.3
E_STW1.5
E_STW1.6
E_STW1.7
E_STW1.10