Description
3.4 Closed-loop control
Danger due to high voltages after a safety shutdown
In spite of a safety shutdown function, the drive may still be operational or high voltages may
still be present.
Residual voltages can result in death, severe injury or significant material damage. The
"Safety shutdown" function can neither ensure that the drive stops immediately nor can it
ensure that residual voltages do not still exist at the output terminals and within the unit.
● Make sure that the drive no longer rotates and that there are no high voltages present.
3.4.3

Description of the components

3.4.3.1

SINAMICS Control Unit

The CU320-2 PN Control Unit is the central control module of the drive's open-loop and closed-
loop control system. The connections are wired internally to the customer terminal block.
3.4.3.2

DRIVE-CLiQ interface

Table 3-1
Pin
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interface: Molex, order number: 85999-3255.
The maximum DRIVE-CLiQ cable length is 50 m.
3.4.3.3

Voltage Sensing Module

The VSM10 Voltage Sensing Module measures the actual line voltage values. The connections
are wired internally to the customer terminal block.
38
WARNING
DRIVE-CLiQ interface
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Technical data
Transmit data +
Transmit data -
Receive data +
Receive data -
Power supply
Electronics ground
SINAMICS GL150 6SL38502UM114PA0Z
Operating Instructions Rev.201910281441 EXAMPLE