Goodrive3000 series medium voltage inverters
Set the torque given filter time.
Function
Name
code
Torque control
forward rotation
P03.14
upper-limit
frequency setting
source selection
Torque control
reverse rotation
P03.15
upper-limit
frequency setting
source selection
Note: 100% of the setting methods 1~9 corresponds to the maximum frequency.
Note: 3, 4, 7 and 8 need to use extension cards.
Function
Name
code
Keypad defined
value of torque
P03.16
control forward
rotation upper-limit
frequency
Keypad defined
value of torque
P03.17
control reverse
rotation upper-limit
frequency
The function code is used to set upper limit of the frequency, 100% corresponding to the maximum
frequency. P03.16 sets P03.14 and P03.17 sets P03.15.
Function
Name
code
Electromotion
P03.18
torque upper-limit
setting source
Braking torque
P03.19
upper-limit setting
source
The function code is used to select electromotion and braking torque upper-limit setting source.
Note: 100% of the setting methods 1~8 corresponds to 3 times of motor rated current.
Detailed instruction of parameters
0: Keypad setting (P03.16 sets
P03.14 and P03.17 sets P03.15)
1: AI1 setting
2: AI2 setting
3: AI3 setting
4: HDI pulse frequency setting
5: Multi-step setting
6: MODBUS communication setting
7: PROFIBUS/CANopen
communication setting
8: Ethernet communication setting
9: Reserved
Detailed instruction of parameters
0.00Hz~P00.03
0.00Hz~P00.03
Detailed instruction of parameters
0: Keypad setting (P03.20 sets
P03.18 and P03.21 sets P03.19)
1: AI1 setting
2: AI2 setting
3: AI3 setting
4: HDI pulse frequency setting
5: MODBUS communication setting
6: PROFIBUS/CANopen
communication setting
7: Ethernet communication setting
8: Reserved
-79-
Goodrive3000 series converter
Default
Setting range
value
0~9
0~9
Default
Setting range
value
0.00~P00.03
50.00Hz
0.00~P00.03
50.00Hz
Default
Setting range
value
0~8
0~8
0
0
0
0
Need help?