Goodrive3000 series medium voltage inverters
P19 Group External temperature detection
Function
Name
code
Motor temperature
P19.00
detection
Motor temperature
P19.01
pre-alarm point
Motor
P19.02
overtemperature
fault point
Motor
P19.03
overtemperature
action
Starting temperature
P19.04
of motor temperature
compensation
Motor temperature
P19.05
compensation
coefficient
Detailed parameter description
0: Invalid
1: PT100
2: PTC
3: Reserved
4: Reserved
0° ~200°
0° ~200°
0: Alarm fault and coast to stop
1: No alarm and keep running
2: No alarm and stop
0~60.0℃
0.0~200.0%
-141-
Goodrive3000 series converter
Setting range
Default
0~4
0° ~200° (0°
pre-alarm invalid)
0° ~200° (0°
pre-alarm invalid)
0~2
0~60.0
40.0℃
0.0~200.0
100.0%
0
125°
150°
0