Goodrive3000 series medium voltage inverters
Current
limit point
Output frequency f
Set
frequency
Function
Name
code
Inverter/Motor
P11.08
underload and
overload pre-alarm
Detection level of
P11.09
overload pre-alarm
Detection time of
P11.10
overload pre-alarm
Detection level of
P11.11
underload pre-alarm
Detection time of
P11.12
underload pre-alarm
Overload pre-alarm signals will be output when the output current of the inverter or motor is higher than
the detection level of overload pre-alarm (P11.09) and the duration exceeds the detection time of
overload pre-alarm (P11.10).
Output current A
Constant speed
ACC
Detailed instruction of parameters
0x000~0x131
LED ones:
0: Motor underload and overload
pre-alarm, relative to motor rated
current
1: Inverter underload and overload
pre-alarm, relative to inverter rated
current
LED tens:
0: Inverter continues running after
underload and overload pre-alarm
1: Inverter continues running after
underload pre-alarm and stop
running after overload fault
2: Inverter continues running after
overload pre-alarm and stop running
after underload fault
3: Inverter stops running after
underload and overload alarm
LED hundreds:
0: Detect all the time
1: Detect in constant running
P11.11~200%
0.1~60.0s
0%~P11.09
0.1~60.0s
-126-
Goodrive3000 series converter
Time t
Time t
Default
Setting range
value
000~131
0x000
P11.11~200
150%
0.1~60.0
0~P11.09
0.1~60.0
1.0s
50%
1.0s