Goodrive3000 series medium voltage inverters
Function
Name
code
7
P10.18
Multi-step speed 8
Running time of step
P10.19
8
P10.20
Multi-step speed 9
Running time of step
P10.21
9
P10.22
Multi-step speed 10 -100.0~100.0%
Running time of step
P10.23
10
P10.24
Multi-step speed 11 -100.0~100.0%
Running time of step
P10.25
11
P10.26
Multi-step speed 12 -100.0~100.0%
Running time of step
P10.27
12
P10.28
Multi-step speed 13 -100.0~100.0%
Running time of step
P10.29
13
P10.30
Multi-step speed 14 -100.0~100.0%
Running time of step
P10.31
14
P10.32
Multi-step speed 15 -100.0~100.0%
Running time of step
P10.33
15
100% of the frequency setting corresponds to the maximum output frequency P00.03.
It is necessary for simple PLC to set P10.02~P10.33 to ensure the running frequency and direction of
each step.
Note: The sign of multi-step speed decides the running direction of simple PLC. Value with minus
indicates reverse running.
Multi-step speed can be set continuously in the range of -f
Goodrive3000 inverters can be set with 16-step speed selected by the combined codes of 1~4 multi-step
terminals, corresponding to multi-step speed 0~15 separately.
Detailed instruction of parameters
-100.0~100.0%
0.0~6553.5s (min)
-100.0~100.0%
0.0~6553.5s (min)
0.0~6553.5s (min)
0.0~6553.5s (min)
0.0~6553.5s (min)
0.0~6553.5s (min)
0.0~6553.5s (min)
0.0~6553.5s (min)
DEC time
(2 steps)
P10.04
P10.02
ACC time
(2 steps)
P10.03
P10.05
P10.07
Goodrive3000 series converter
P10.28
P10.30
P10.06
P10.31
P10.33
~f
max
max
-121-
Default
Setting range
value
-100.0~100.0
0.0%
0.0~6553.5
0.0s
-100.0~100.0
0.0%
0.0~6553.5
0.0s
-100.0~100.0
0.0%
0.0~6553.5
0.0s
-100.0~100.0
0.0%
0.0~6553.5
0.0s
-100.0~100.0
0.0%
0.0~6553.5
0.0s
-100.0~100.0
0.0%
0.0~6553.5
0.0s
-100.0~100.0
0.0%
0.0~6553.5
0.0s
-100.0~100.0
0.0%
0.0~6553.5
0.0s
P1032