Goose Function Block To Receive A Measurand Value Goosemvrcv - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 16
Station communication
16.7
16.7.1
16.7.2
16.7.3
530
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a
cross to receive the integer values.
The implementation for IEC61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
GOOSE function block to receive a measurand value
GOOSEMVRCV
Identification
Function description
GOOSE function block to receive a
measurand value
Functionality
GOOSEMVRCV is used to receive measured value using IEC61850 protocol via
GOOSE.
Function block
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251-1-en.vsd
IEC10000251 V1 EN
Figure 242:
GOOSEMVRCV function block
IEC 61850
IEC 60617
identification
identification
GOOSEMVRCV
-
1MRK 502 043-UUS B
ANSI/IEEE C37.2
device number
-
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents