Controllable Gate Function Block Gate - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Table 249:
PULSETIMER Non group settings (basic)
Name
Values (Range)
t
0.000 - 90000.000
13.3.1.5
Technical Manual
Functionality
The pulse function can be used, for example for pulse extensions or limiting of
operation of outputs. The PULSETIMER has a settable length.
Function block
PULSETIMER
INPUT
OUT
IEC09000291-1-en.vsd
IEC09000291 V1 EN
Figure 173:
PULSETIMER function block
Signals
Table 247:
PULSETIMER Input signals
Name
Type
INPUT
BOOLEAN
Table 248:
PULSETIMER Output signals
Name
Type
OUT
BOOLEAN
Settings
Unit
Step
s
0.001

Controllable gate function block GATE

Identification
Function description
Controllable gate function block
Functionality
The GATE function block is used for controlling if a signal should pass from the input
to the output or not, depending on setting.
Default
Description
0
Input signal
Description
Output signal
Default
Description
0.010
Pulse time length
IEC 61850
IEC 60617
identification
identification
GATE
Section 13
Logic
ANSI/IEEE C37.2
device number
-
-
371