Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 14
Monitoring
14.13.4
14.13.5
Table 349:
SPVNZBAT Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
RtdBattVolt
20.00 - 250.00
BattVoltLowLim
60 - 140
BattVoltHiLim
60 - 140
tDelay
0.000 - 60.000
tReset
0.000 - 60.000
474
In the definite time (DT) mode, SPVNZBAT operates after a predefined operate time
and resets when the battery undervoltage or overvoltage condition disappears after
reset time.

Signals

Table 347:
SPVNZBAT Input signals
Name
Type
V_BATT
REAL
BLOCK
BOOLEAN
Table 348:
SPVNZBAT Output signals
Name
Type
AL_VLOW
BOOLEAN
AL_VHI
BOOLEAN
PU_VLOW
BOOLEAN
PU_VHI
BOOLEAN
Settings
Unit
Step
-
-
V
1.00
%Vbat
1
%Vbat
1
s
0.001
s
0.001
Default
Description
0.00
Battery terminal voltage that has to be supervised
0
Blocks all the output signals of the function
Description
Alarm when voltage has been below low limit for a set
time
Alarm when voltage has exceeded high limit for a set
time
Pick up signal when battery voltage drops below lower
limit
Pick up signal when battery voltage exceeds upper limit
Default
Description
Enabled
Disable/Enable Operation
110.00
Battery rated voltage
70
Lower limit for the battery terminal voltage
120
Upper limit for the battery terminal voltage
0.200
Delay time for alarm
0.000
Time delay for reset of alarm
1MRK 502 043-UUS B
Technical Manual