Directional Supervision Element With Integrated Directional Comparison Function - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
8.2.7.8
Technical Manual
available. For the complete list of available inverse curves please refer to section
"Inverse time
characteristics".
Time delay related settings. By these parameter settings the properties like definite
time delay, minimum operating time for inverse curves and reset time delay are
defined.
Supervision by second harmonic blocking feature (Enabled/Disabled). By this
parameter setting it is possible to prevent operation of the step if the second
harmonic content in the residual current exceeds the preset level.
Simplified logic diagram for one residual overcurrent step is shown in figure 84.
|I
|
OP
Pickupx
BLKx
BLOCK
2ndH_BLOCK_Int
HarmRestrainx=Disabled
DirModeSelx=Disabled
DirModeSelx=Non-directional
DirModeSelx=Forward
DirModeSelx=Reverse
ANSI09000638 V2 EN
Figure 84:
Simplified logic diagram for residual overcurrent
The protection can be completely blocked from the binary input BLOCK. Output
signals for respective step, PU_STx and TRSTx and , can be blocked from the binary
input BLKn.
Directional supervision element with integrated directional comparison
function
It shall be noted that at least one of the four residual overcurrent steps
shall be set as directional in order to enable execution of the directional
supervision element and the integrated directional comparison function.
The protection has integrated directional feature. The operating quantity current
I3PDIR is always used. The polarizinwcg method is determined by the parameter
Characteristn=DefTime
a
a>b
b
AND
Characteristn=Inverse
OR
STEPx_DIR_Int
OR
AND
OR
FORWARD_Int
AND
REVERSE_Int
Section 8
Current protection
0-tx
0
OR
Inverse
ANSI09000638-2-en.vsd
PU_ST
x
189