Time tagging

The IED has a built-in real-time calendar and clock. This function is used for all time
tagging within the disturbance report
Recording times
Disturbance report DRPRDRE records information about a disturbance during a
settable time frame. The recording times are valid for the whole disturbance report.
Disturbance recorder, event recorder and indication function register disturbance data
and events during tRecording, the total recording time.
The total recording time, tRecording, of a recorded disturbance is:
PreFaultrecT + tFault + PostFaultrecT or PreFaultrecT + TimeLimit , depending on
tRecording =
which criterion stops the current disturbance recording
Trig point
PreFaultRecT
1
IEC05000487 V1 EN
Figure 205:
The recording times definition
PreFaultRecT, 1
Pre-fault or pre-trigger recording time. The time before the fault including the operate
time of the trigger. Use the setting
tFault, 2
Fault time of the recording. The fault time cannot be set. It continues as long as any
valid trigger condition, binary or analog, persists (unless limited by
time).
PostFaultRecT, 3 Post fault recording time. The time the disturbance recording continues after all
activated triggers are reset. Use the setting
TimeLimit
Limit time. The maximum allowed recording time after the disturbance recording was
triggered. The limit time is used to eliminate the consequences of a trigger that does
not reset within a reasonable time interval. It limits the maximum recording time of a
recording and prevents subsequent overwriting of already stored disturbances. Use the
TimeLimit to set this time.
setting
TimeLimit
PostFaultRecT
2
PreFaultRecT to set this time.
Section 14
Monitoring
3
en05000487.vsd
TimeLimit the limit
PostFaultRecT to set this time.
451