Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
7.1.5
Table 42:
ZGCPDIS (21G) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
ImpedanceAng
0.00 - 90.00
OpModeZ1
Disable-Zone
Enable-Zone
Z1Fwd
0.005 - 3000.000
Z1Rev
0.005 - 3000.000
tZ1
0.000 - 60.000
OpModeZ2
Disable-Zone
Enable-Zone
Z2Fwd
0.005 - 3000.000
Z2Rev
0.005 - 3000.000
tZ2
0.000 - 60.000
OpModeZ3
Disable-Zone
Enable-Zone
Z3Fwd
0.005 - 3000.000
Z3Rev
0.005 - 3000.000
tZ3
0.000 - 60.000
Table 43:
ZGCPDIS (21G) Group settings (advanced)
Name
Values (Range)
LoadEnchModeZ3
Disabled
Enabled
Technical Manual
Table 41:
ZGCPDIS (21G) Output signals
Name
Type
TRIP
BOOLEAN
TRZ1
BOOLEAN
TRZ2
BOOLEAN
TRZ3
BOOLEAN
PICKUP
BOOLEAN
PU_Z1
BOOLEAN
PU_Z2
BOOLEAN
Z3_PU
BOOLEAN

Settings

Unit
Step
-
-
Deg
0.01
-
-
ohm/p
0.001
ohm/p
0.001
s
0.001
-
-
ohm/p
0.001
ohm/p
0.001
s
0.001
-
-
ohm/p
0.001
ohm/p
0.001
s
0.001
Unit
Step
-
-
Description
General trip
Trip signal Zone1
Trip signal Zone2
Trip signal Zone3
Pickup
Start signal Zone1
Start signal Zone2
Start signal Zone3
Default
Description
Disabled
Disable/Enable Operation
80.00
Impedance angle in degrees, common for all
zones
Disable-Zone
Operation mode of Zone 1
30.000
Forward reach setting for Zone 1
30.000
Reverse reach setting for Zone 1
0.100
Time delay to operate for Zone 1
Disable-Zone
Operation mode of Zone 2
30.000
Forward reach setting for Zone 2
30.000
Reverse reach setting for Zone 2
0.500
Time delay to operate for Zone 2
Disable-Zone
Operation mode of Zone 3
30.000
Forward reach setting for Zone 3
30.000
Reverse reach setting for Zone 3
1.000
Time delay to operate for Zone 3
Default
Description
Disabled
Enable load enchroachment mode Zone 3
Section 7
Impedance protection
135