Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 16
Station communication
16.5.5
Table 404:
GOOSEDPRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
16.5.6
16.6
16.6.1
528

Settings

Unit
Step
-
-
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a
cross to receive the double point values.
The implementation for IEC61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
GOOSE function block to receive an integer value
GOOSEINTRCV
Identification
Function description
GOOSE function block to receive an
integer value
Default
Description
Disabled
Operation Enable/Disable
IEC 61850
IEC 60617
identification
identification
GOOSEINTRCV
-
1MRK 502 043-UUS B
ANSI/IEEE C37.2
device number
-
Technical Manual