Simplified Logic Diagrams - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 7
Impedance protection
7.4.6.2
164
LdAngle
LdAngle
RLd
ANSI10000144 V2 EN
Figure 77:
Characteristic of load encroachment function
The reach is limited by the minimum operation current and the distance measuring zones.

Simplified logic diagrams

Figure
78
schematically presents the creation of the phase-to-phase operating conditions.
X
RLd
LdAngle
R
LdAngle
ANSI10000144-2-en.vsd
1MRK 502 043-UUS B
Technical Manual