Settings - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
12.2.3.5
Table 202:
LOCREM Non group settings (basic)
Name
Values (Range)
ControlMode
Internal LR-switch
External LR-switch
12.2.4
12.2.4.1
12.2.4.2
12.2.4.3
Technical Manual

Settings

Unit
Step
-
-
Local remote control LOCREMCTRL
Identification
Function description
Local remote control
Functionality
The signals from the local HMI or from an external local/remote switch are applied via
the function blocks LOCREM and LOCREMCTRL to the Bay control (QCBAY)
function block. A parameter in function block LOCREM is set to choose if the switch
signals are coming from the local HMI or from an external hardware switch connected
via binary inputs.
Function block
LOCREMCTRL
^PSTO1
^HMICTR1
^PSTO2
^HMICTR2
^PSTO3
^HMICTR3
^PSTO4
^HMICTR4
^PSTO5
^HMICTR5
^PSTO6
^HMICTR6
^PSTO7
^HMICTR7
^PSTO8
^HMICTR8
^PSTO9
^HMICTR9
^PSTO10
^HMICTR10
^PSTO11
^HMICTR11
^PSTO12
^HMICTR12
IEC09000074_1_en.vsd
IEC09000074 V1 EN
Figure 156:
LOCREMCTRL function block
Default
Description
Internal LR-switch
Control mode for internal/external LR-switch
IEC 61850
IEC 60617
identification
identification
LOCREMCTRL
-
Section 12
Control
ANSI/IEEE C37.2
device number
-
337