Section 11
Secondary system supervision
11.1.3
11.1.4
304
A criterion based on delta current and delta voltage measurements can be added to the
fuse failure supervision function in order to detect a three phase fuse failure, which in
practice is more associated with voltage transformer switching during station operations.

Function block

SDDRFUF
I3P*
BLKZ
V3P*
BLKV
BLOCK
3PH
52A
DLD1PH
MCBOP
DLD3PH
89B
ANSI08000220-1-en.vsd
ANSI08000220 V1 EN
Figure 141:
SDDRFUF function block
Signals
Table 181:
SDDRFUF Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
52a
BOOLEAN
MCBOP
BOOLEAN
89b
BOOLEAN
Table 182:
SDDRFUF Output signals
Name
Type
BLKZ
BOOLEAN
BLKV
BOOLEAN
3PH
BOOLEAN
DLD1PH
BOOLEAN
DLD3PH
BOOLEAN
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Active when circuit breaker is closed
0
Active when external Miniature Circuit Breaker opens
protected voltage circuit
0
Active when line disconnect switch is open
Description
Start of current and voltage controlled function
General pickup
Three-phase pickup
Dead line condition in at least one phase
Dead line condition in all three phases
1MRK 502 043-UUS B
Technical Manual