Section 9
Voltage protection
9.5.5
Table 163:
STEFPHIZ (59THD) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
Beta
0.50 - 10.00
CBexists
No
Yes
FactorCBopen
1.00 - 10.00
VN3rdHPU
0.5 - 10.0
VT3BlkLevel
0.1 - 10.0
VNFundPU
1.0 - 50.0
t3rdH
0.020 - 60.000
tVNFund
0.020 - 60.000
Table 164:
STEFPHIZ (59THD) Non group settings (basic)
Name
Values (Range)
GlobalBaseSel
1 - 6
TVoltType
NoVoltage
ResidualVoltage
AllThreePhases
PhaseA
PhaseB
PhaseC
284

Settings

Unit
Step
-
-
-
0.01
-
-
-
0.01
%
0.1
%
0.1
%
0.1
s
0.001
s
0.001
Unit
Step
-
1
-
-
Default
Description
Disabled
Disable/Enable Operation
3.00
Portion of 3rd harm voltage in neutral point
used as bias
No
Defines if generator CB exists (between Gen
& Transformer)
1.00
Beta is multiplied by this factor when CB is
open
2.0
Pickup 3rd Harm V< protection (when
activated) % of VB/1,732
1.0
If VT3 is below limit 3rdH Diff is blocked, in %
of VB/1,732
5.0
Pickup fundamental VN> protection (95%
SEF), % of VB/1,732
1.000
Operation delay of 3rd harm-based protection
(100% SEF) in s
0.500
Operation delay of fundamental VN>
protection (95% SEF) in s
Default
Description
1
Selection of one of the Global Base Value
groups
ResidualVoltage
Used connection type for gen. terminal
voltage transformer
1MRK 502 043-UUS B
Technical Manual