Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 8
Current protection
8.7.2.3
8.7.2.4
Table 106:
GOPPDOP (32) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpMode1
Disabled
OverPower
Power1
0.0 - 500.0
Angle1
-180.0 - 180.0
TripDelay1
0.010 - 6000.000
OpMode2
Disabled
OverPower
Table continues on next page
226

Signals

Table 104:
GOPPDOP (32) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLK1
BOOLEAN
BLK2
BOOLEAN
Table 105:
GOPPDOP (32) Output signals
Name
Type
TRIP
BOOLEAN
TRIP1
BOOLEAN
TRIP2
BOOLEAN
BFI_3P
BOOLEAN
PICKUP1
BOOLEAN
PICKUP2
BOOLEAN
P
REAL
PPERCENT
REAL
Q
REAL
QPERCENT
REAL
Settings
Unit
Step
-
-
-
-
%
0.1
Deg
0.1
s
0.001
-
-
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Block of step 1
0
Block of step 2
Description
Common trip signal
Trip signal from stage 1
Trip signal from stage 2
General pickup signal
Pickup signal from stage 1
Pickup signal from stage 2
Active Power
Active power in % of calculated power base value
Reactive power
Reactive power in % of calculated power base value
Default
Description
Disabled
Operation Disable / Enable
OverPower
Operation mode 1
1.0
Power setting for stage 1 in % of calculated
power base value
0.0
Characteristic angle for stage 1
1.000
Trip delay for stage 1
OverPower
Operation mode 2
1MRK 502 043-UUS B
Technical Manual