The input of this GOOSE block must be linked in SMT by means of a cross
to receive the double point values.
The implementation for IEC61850 quality data handling is restricted to a
simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
GOOSE function block to receive an integer value
GOOSEINTRCV
Identification
Function description
GOOSE function block to receive an
integer value
Functionality
GOOSEINTRCV is used to receive an integer value using IEC61850 protocol via
GOOSE.
Function block
GOOSEINTRCV
BLOCK
^INTOUT
DATAVALID
COMMVALID
TEST
IEC10000250-1-en.vsd
IEC10000250 V1 EN
Figure 339:
GOOSEINTRCV function block
Station communication
IEC 61850
IEC 60617
identification
identification
GOOSEINTRCV
-
Section 16
ANSI/IEEE C37.2
device number
-
727