Section 6
Differential protection
6.1.2.4
Table 24:
T3WPDIF (87T) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
IdMin
0.10 - 0.60
EndSection1
0.20 - 1.50
EndSection2
1.00 - 10.00
SlopeSection2
10.0 - 50.0
SlopeSection3
30.0 - 100.0
IdUnre
1.00 - 50.00
I2/I1Ratio
5.0 - 100.0
I5/I1Ratio
5.0 - 100.0
CrossBlockEn
Disabled
Enabled
NegSeqDiffEn
Disabled
Enabled
IMinNegSeq
0.02 - 0.20
NegSeqROA
30.0 - 90.0
SOTFMode
Disabled
Enabled
IDiffAlarm
0.05 - 1.00
tAlarmDelay
0.000 - 60.000
Table 25:
T3WPDIF (87T) Non group settings (basic)
Name
Values (Range)
GlobalBaseSelW1
1 - 6
GlobalBaseSelW2
1 - 6
GlobalBaseSelW3
1 - 6
ConnectTypeW1
WYE (Y)
Delta (D)
Table continues on next page
80

Settings

Unit
Step
-
-
IB
0.01
IB
0.01
IB
0.01
%
0.1
%
0.1
IB
0.01
%
0.1
%
0.1
-
-
-
-
IB
0.01
Deg
0.1
-
-
IB
0.01
s
0.001
Unit
Step
-
1
-
1
-
1
-
-
Default
Description
Disabled
Operation Disable / Enable
0.30
Section 1 sensitivity current, usually W1
current
1.25
End of section 1, multiple of W1 rated current
3.00
End of section 2, multiple of W1 rated current
40.0
Slope in section 2 of operate-restrain
characteristics
80.0
Slope in section 3 of operate-restrain
characteristics
10.00
Unrestrained protection limit, multiple of W1
rated current
15.0
Maximum ratio of 2nd harmonic to
fundamental harmonic differential current
25.0
Maximum ratio of 5th harmonic to
fundamental harmonic differential current
Enabled
Operation Off/On for cross-block logic
between phases
Enabled
Operation Off/On for negative sequence
differential function
0.04
Minimum negative sequence current
60.0
Operate angle for internal/external negative
sequence fault discriminator
Enabled
Operation mode for switch onto fault function
0.20
Differential current alarm, multiple of base
current, usually W1 current
10.000
Time delay for differential current alarm
Default
Description
1
Selection of one of the Global Base Value
groups, winding 1
1
Selection of one of the Global Base Value
groups, winding 2
1
Selection of one of the Global Base Value
groups, winding 3
WYE (Y)
Connection type of winding 1: Y-wye or D-delta
1MRK 502 043-UUS B