Monitored Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Name
Values (Range)
AccCurrAlmLvl
0.00 - 20000.00
AccCurrLO
0.00 - 20000.00
DirCoef
-3.00 - -0.50
LifeAlmLevel
0 - 99999
OpNumRatCurr
1 - 99999
OpNumFaultCurr
1 - 10000
OpNumAlm
0 - 9999
OpNumLO
0 - 9999
tOpenAlm
0 - 200
tCloseAlm
0 - 200
OpenTimeCorr
0 - 100
CloseTimeCorr
0 - 100
DifTimeCorr
-10 - 10
tSprngChrgAlm
0.00 - 60.00
tPressAlm
0.00 - 60.00
TPressLO
0.00 - 60.00
AccEnerInitVal
0.00 - 9999.99
CountInitVal
0 - 9999
CBRemLife
0 - 9999
InactDayAlm
0 - 9999
InactDayInit
0 - 9999
InactHourAlm
0 - 23
14.16.6
Technical Manual
Unit
Step
-
0.01
-
0.01
-
0.01
-
1
-
1
-
1
-
1
-
1
ms
1
ms
1
ms
1
ms
1
ms
1
s
0.01
s
0.01
s
0.01
-
0.01
-
1
-
1
Day
1
Day
1
Hour
1

Monitored data

Table 364:
SSCBR Monitored data
Name
Type
CBOTRVT
REAL
CBCLTRVT
REAL
SPRCHRT
REAL
NO_OPR
INTEGER
Table continues on next page
Default
Description
2500.00
Setting of alarm level for accumulated
currents power
2500.00
Lockout limit setting for accumulated currents
power
-1.50
Directional coefficient for CB life calculation
5000
Alarm level for CB remaining life
10000
Number of operations possible at rated current
1000
Number of operations possible at rated fault
current
200
Alarm limit for number of operations
300
Lockout limit for number of operations
40
Alarm level setting for open travel time
40
Alarm level setting for close travel time
10
Correction factor for open travel time
10
Correction factor for CB close travel time
5
Correction factor for time difference in
auxiliary and main contacts open time
1.00
Setting of alarm for spring charging time
0.10
Time delay for gas pressure alarm
0.10
Time delay for gas pressure lockout
0.00
Accumulation energy initial value
0
Operation numbers counter initialization value
5000
Initial value for the CB remaining life estimates
2000
Alarm limit value of the inactive days counter
0
Initial value of the inactive days counter
0
Alarm time of the inactive days counter in hours
Values (Range)
Unit
-
ms
-
ms
-
s
-
-
Section 14
Monitoring
Description
Travel time of the CB during
opening operation
Travel time of the CB during
closing operation
The charging time of the CB
spring
Number of CB operation cycle