Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
16.7.4
16.7.5
Table 410:
GOOSEMVRCV Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
16.7.6
Technical Manual

Signals

Table 408:
GOOSEMVRCV Input signals
Name
Type
BLOCK
BOOLEAN
Table 409:
GOOSEMVRCV Output signals
Name
Type
MVOUT
REAL
DATAVALID
BOOLEAN
COMMVALID
BOOLEAN
TEST
BOOLEAN
Settings
Unit
Step
-
-
Operation principle
The DATAVALID output will be HIGH if the incoming message is with valid data.
The COMMVALID output will become LOW when the sending IED is under total
failure condition and the GOOSE transmission from the sending IED does not happen.
The TEST output will go HIGH if the sending IED is in test mode.
The input of this GOOSE block must be linked in SMT by means of a
cross to receive the float values.
The implementation for IEC61850 quality data handling is restricted to
a simple level. If quality data validity is GOOD then the DATAVALID
output will be HIGH. If quality data validity is INVALID,
QUESTIONABLE, OVERFLOW, FAILURE or OLD DATA then the
DATAVALID output will be LOW.
Station communication
Default
Description
0
Block of function
Description
Measurand value output
Data valid for measurand value output
Communication valid for measurand value output
Test output
Default
Description
Disabled
Operation Enable/Disable
Section 16
531