Function controlled by SetLEDn setting in Disturbance report function.
Indication list:
The possible indication signals are the same as the ones chosen for the disturbance
report function and disturbance recorder.
The indication function tracks 0 to 1 changes of binary signals during the recording
period of the collection window. This means that constant logic zero, constant logic
one or state changes from logic one to logic zero will not be visible in the list of
indications. Signals are not time tagged. In order to be recorded in the list of
indications the:
the signal must be connected to binary input BxRBDR function block
the DRPRDRE parameter Operation must be set Enabled
the DRPRDRE must be trigged (binary or analog)
the input signal must change state from logical 0 to 1 during the recording time.
Indications are selected with the indication mask (IndicationMask) when setting the
binary inputs.
The name of the binary signal that appears in the Indication function is the user-defined
name assigned at configuration of the IED. The same name is used in disturbance
recorder function, indications and event recorder function.

Technical data

Table 332:
DRPRDRE technical data
Function
Buffer capacity
Event recorder
Functionality
Quick, complete and reliable information about disturbances in the primary and/or in
the secondary system is vital, for example, time-tagged events logged during
disturbances. This information is used for different purposes in the short term (for
example corrective actions) and in the long term (for example functional analysis).
Maximum number of indications presented
for single disturbance
Maximum number of recorded disturbances
Section 14
Monitoring
Value
96
100
457