Binary Inputs - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
18.2.3
Technical Manual
Table 459:
Auxiliary voltage supply of 48-125 V DC
Case
3U full 19"

Binary inputs

The binary inputs can be used, for example, to generate a blocking signal, to unlatch
output contacts, to trigger the digital fault recorder or for remote control of IED
settings.
Each signal connector terminal is connected with one 14 or 16 Gauge wire.
Table 460:
Binary inputs X304, 3U full 19"
Terminal
Description
X304-1
Common - for inputs 1-3
X304-2
Binary input 1 +
X304-3
Binary input 2 +
X304-4
Binary input 3 +
X304-5
Common - for inputs 4-6
X304-6
Binary input 4 +
X304-7
Binary input 5 +
X304-8
Binary input 6 +
X304-9
Common - for inputs 7-9
X304-10
Binary input 7 +
X304-11
Binary input 8 +
X304-12
Binary input 9 +
X304-13
Common - for inputs 10-12
X304-14
Binary input 10 +
X304-15
Binary input 11 +
X304-16
Binary input 12 +
IED physical connections
Terminal
X420-1
X420-2
Hardware module
instance
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
COM_101
Section 18
Description
- Input
+ Input
PCM600 info
Hardware channel
BI1
BI2
BI3
BI4
BI5
BI6
BI7
BI8
BI9
BI10
BI11
BI12
583