Section 14
Monitoring
14.3.2.2
14.3.2.3
14.3.2.4
Table 319:
DRPRDRE Non group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
PreFaultRecT
0.05 - 3.00
PostFaultRecT
0.1 - 10.0
TimeLimit
0.5 - 8.0
PostRetrig
Disabled
Enabled
MaxNoStoreRec
10 - 100
ZeroAngleRef
1 - 30
OpModeTest
Disabled
Enabled
426

Function block

DRPRDRE
DRPOFF
RECSTART
RECMADE
CLEARED
MEMUSED
IEC09000346-1-en.vsd
IEC09000346 V1 EN
Figure 200:
DRPRDRE function block
Signals
Table 318:
DRPRDRE Output signals
Name
Type
DRPOFF
BOOLEAN
RECSTART
BOOLEAN
RECMADE
BOOLEAN
CLEARED
BOOLEAN
MEMUSED
BOOLEAN
Settings
Unit
Step
-
-
s
0.01
s
0.1
s
0.1
-
-
-
1
Ch
1
-
-
Description
Disturbance report function turned off
Disturbance recording started
Disturbance recording made
All disturbances in the disturbance report cleared
More than 80% of memory used
Default
Description
Disabled
Operation Enable/Disable
0.10
Pre-fault recording time
0.5
Post-fault recording time
1.0
Fault recording time limit
Disabled
Post-fault retrig enabled (On) or not (Off)
100
Maximum number of stored disturbances
1
Trip value recorder, phasor reference channel
Disabled
Operation mode during test mode
1MRK 502 043-UUS B
Technical Manual