ABB REG650 Technical Manual page 106

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 6
Differential protection
100
operate region on the operate - restrain characteristic. So, this protection is not
independent of the traditional restrained differential protection - it is activated after the
first start signal has been placed.
If the fault is positively recognized as internal, then the unrestrained negative sequence
differential protection places its own trip request.
If the bias current is higher than 110% of IBase of the power transformer winding W1,
then any block signals by the harmonic and/or waveform blocking criteria are
overridden, and the differential protection operates quickly without any further delay.
If the bias current is lower than 110% of IBase, the negative sequence differential
protection is restrained by any harmonic block signal.
This logic guarantees a fast disconnection of a faulty power transformer for any heavy
faults.
If a fault is classified as external, the further analysis of the fault conditions is initiated.
If all the instantaneous differential currents in phases where pickup signals have been
issued are free of harmonic pollution, then a (minor) internal fault, simultaneous with a
predominant external fault can be suspected. If the differential current is above the
restrain limit a trip will be issued.
During external faults, major false differential currents can only exist when one or
more current transformers saturate. In this case, the false instantaneous differential
currents are polluted by higher harmonic components, the 2
differential protection will block the trip operation based on the blocking criteria.
Sensitive negative sequence based turn-to-turn fault protection
The sensitive, negative sequence current based turn-to-turn fault protection detects the
low level faults, which are not detected by the traditional differential protection until
they develop into more severe faults, including power transformer iron core. The
sensitive protection is independent from the traditional differential protection and is a
very good complement to it. The essential part of this sensitive protection is the internal/
external fault discriminator. In order to be activated, the sensitive protection requires
no pickup signal from the traditional power transformer biased differential protection.
If magnitudes of HV and LV negative sequence current contributions are above the set
limit for IminNegSeq, then their relative positions are determined. If the disturbance is
characterized as an internal fault, then a separate trip request will be placed. Any
decision on the way to the final trip request must be confirmed several times in
succession in order to cope with eventual CT transients. This causes a short additional
operating time delay due to this security count. For very low level turn-to-turn faults
the overall response time of this protection is about 30ms. The sensitive negative
sequence differential protection is automatically deactivated if the bias current
becomes higher than 150 % IBase. Further, this protection can always be restrained by
any harmonic block signal. This because at rather low fault currents, which are to be
detected by this protection, harmonic pollution is not likely.
1MRK 502 043-UUS B
nd
th
, the 5
and so on and the
Technical Manual