ABB REG650 Technical Manual page 199

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
0.6
X
IDirPU
X
0.4
polMethod=Voltage
polMethod=Dual
polMethod=Current
BLOCK
ANSI07000067 V4 EN
Figure 88:
Simplified logic diagram for directional supervision element with integrated directional comparison step
Technical Manual
1.
PUFW=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger
than setting parameter IDirPU and directional supervision element detects fault in
forward direction.
2.
PUREV=1 when operating quantity magnitude Iop x cos(φ - AngleRCA) is bigger
than 60% of setting parameter IDirPU and directional supervision element detects
fault in reverse direction.
These signals shall be used for communication based ground-fault teleprotection
communication schemes (permissive or blocking).
Simplified logic diagram for directional supervision element with integrated directional
comparison step is shown in figure 88:
|
|
IopDir
a
a>b
b
a
a>b
b
OR
OR
IPol
T
0.0
F
RNPol
X
Complex
Number
XNPol
AND
REVERSE_Int
AND
FORWARD_Int
AngleRCA
VPolMin
IPolMin
VPol
T
I3PDIR
0.0
F
VTPol
VIPol
STAGE1_DIR_Int
T
STAGE2_DIR_Int
0.0
F
STAGE3_DIR_Int
STAGE4_DIR_Int
Section 8
Current protection
PUREV
PUFW
FWD
AND
FORWARD_Int
AND
REVERSE_Int
RVS
OR
AND
ANSI07000067-4-en.vsd
193

Advertisement

Table of Contents
loading

Table of Contents