Monitored Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 8
Current protection
8.2.6
8.2.7
8.2.7.1
182

Monitored data

Table 77:
EF4PTOC (51N_67N) Monitored data
Name
Type
STDIR
INTEGER
IOp
REAL
VPol
REAL
IPol
REAL
VPolIang
REAL
IPOLIANG
REAL
IOPDIR
REAL
Operation principle
Four step residual overcurrent protection, zero or negative sequence direction
EF4PTOC (51N/67N) function has the following four "Analog Inputs" on its function
block in the configuration tool:
1.
I3P, input used for "Operating Quantity".
2.
V3P, input used for "Voltage Polarizing Quantity".
3.
I3PPOL, input used for "Current Polarizing Quantity".
4.
I3PDIR, input used for "Operating Directional Quantity".
These inputs are connected from the corresponding pre-processing function blocks in
the Configuration Tool within PCM600.
Operating quantity within the function
If the function is set to measure zero sequence, it uses Residual Current (3I
operating quantity. The residual current can be:
1.
directly measured (when a dedicated CT input of the IED is connected in PCM600
to the fourth analog input of the pre-processing block connected to EF4PTOC (51N/
67N) function input I3P). This dedicated IED CT input can be for example,
connected to:
Values (Range)
Unit
0=No direction
-
1=Forward
2=Reverse
3=Both
-
A
-
kV
-
A
-
deg
-
deg
-
A
1MRK 502 043-UUS B
Description
Fault direction coded as
integer
Operating current level
Polarizing voltage level
Polarizing current level
Angle between polarizing
voltage and operating current
Angle between polarizing
current and operating current
Amplitude of the directional
operating quantity
) for its
0
Technical Manual