Selector Mini Switch Vsggio - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
12.4
12.4.1
12.4.2
12.4.3
12.4.4
Technical Manual
through the PSTO input. If any operation is allowed the signal INTONE from the
Fixed signal function block can be connected. SLGGIO function block has also an
integer value output, that generates the actual position number. The positions and the
block names are fully settable by the user. These names will appear in the menu, so the
user can see the position names instead of a number.

Selector mini switch VSGGIO

Identification
Function description
Selector mini switch
Functionality
The Selector mini switch VSGGIO function block is a multipurpose function used for a
variety of applications, as a general purpose switch.
VSGGIO can be controlled from the menu or from a symbol on the single line diagram
(SLD) on the local HMI.
Function block
VSGGIO
BLOCK
BLOCKED
PSTO
POSITION
IPOS1
POS1
IPOS2
POS2
CMDPOS12
CMDPOS21
IEC09000341-1-en.vsd
IEC09000341 V1 EN
Signals
Table 210:
VSGGIO Input signals
Name
Type
BLOCK
BOOLEAN
PSTO
INTEGER
IPOS1
BOOLEAN
IPOS2
BOOLEAN
IEC 61850
IEC 60617
identification
identification
VSGGIO
-
Default
Description
0
Block of function
0
Operator place selection
0
Position 1 indicating input
0
Position 2 indicating input
Section 12
Control
ANSI/IEEE C37.2
device number
-
345

Advertisement

Table of Contents
loading

Table of Contents