An open CT circuit condition creates unexpected operations for Generator differential
protection under the normal load conditions. It is also possible to damage secondary
equipment due to high voltage produced from open CT circuit outputs. Therefore, it
may be a requirement from security and reliability points of view to have open CT
detection function to block Generator differential protection function in case of open
CT conditions and at the same time produce the alarm signal to the operational
personal to make quick remedy actions to correct the open CT condition.
Generator differential protection GENPDIF (87G) is also well suited to generate fast,
sensitive and selective fault clearance, if used to protect shunt reactors or small busduct.

Function block

GENPDIF (87G)
I3PNCT*
TRIP
I3PTCT*
TRIPRES
BLOCK
TRIPUNRE
BLKRES
TRNSUNR
BLKUNRES
TRNSSENS
BLKNSUNR
PICKUP
BLKNSSEN
BLKH
DESENSIT
OPENCT
OPENCTAL
IDMAG_A
IDMAG_B
IDMAG_C
IDMAG_NS
IBIAS
ANSI07000025-2-en.vsd
ANSI07000025 V3 EN
Figure 45:
GENPDIF (87G) function block
Signals
Table 34:
GENPDIF (87G) Input signals
Name
Type
I3PNCT
GROUP
SIGNAL
I3PTCT
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKRES
BOOLEAN
BLKUNRES
BOOLEAN
BLKNSUNR
BOOLEAN
BLKNSSEN
BOOLEAN
DESENSIT
BOOLEAN
Default
Description
-
Neutral side CT input
-
Terminal side CT input
0
Block of function
0
Block of trip from the restrained diff. protection
0
Block of trip from unrestrained diff. prot.
0
Block of trip for unrestrained negative sequence
differential protection
0
Block of trip for sensitive negative sequence
differential protection
0
Raise pick up: function temporarily desensitized
Section 6
Differential protection