Section 19 Technical Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

1MRK 502 043-UUS B
Section 19
19.1
19.2
Technical Manual
Technical data
Dimensions
Table 478:
Dimensions of the IED - 3U full 19" rack
Description
Width
Height
Depth
Weight box
Weight LHMI
Power supply
Table 479:
Power supply
Description
V
n
V
variation
n
Maximum load of auxiliary voltage
supply
Ripple in the DC auxiliary voltage
Maximum interruption time in the
auxiliary DC voltage without
resetting the IED
Value
17.40 inches (442 mm)
5.20 inches (132 mm), 3U
9.82 inches (249.5 mm)
<22.04 lbs (10 kg)
2.87 lbs (1.3 kg)
600PSM02
48, 60, 110, 125 V DC
80...120% of V
(38.4...150 V
n
DC)
35 W for DC
40 W for AC
Max 15% of the DC value (at frequency of 100 and 120 Hz)
50 ms at V
n
Section 19
Technical data
600PSM03
100, 110, 120, 220, 240 V AC,
50 and 60 Hz
110, 125, 220, 250 V DC
85...110% of V
(85...264 V AC)
n
80...120% of V
(88...300 V DC)
n
621