Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 14
Monitoring
14.11.4
14.11.5
Table 342:
MVGGIO Non group settings (basic)
Name
Values (Range)
BasePrefix
micro
milli
unit
kilo
Mega
Giga
Tera
MV db
1 - 300
MV zeroDb
0 - 100000
MV hhLim
-5000.00 - 5000.00
MV hLim
-5000.00 - 5000.00
MV lLim
-5000.00 - 5000.00
MV llLim
-5000.00 - 5000.00
MV min
-5000.00 - 5000.00
MV max
-5000.00 - 5000.00
MV dbType
Cyclic
Dead band
Int deadband
MV limHys
0.000 - 100.000
470

Signals

Table 340:
MVGGIO Input signals
Name
Type
BLOCK
BOOLEAN
IN
REAL
Table 341:
MVGGIO Output signals
Name
Type
VALUE
REAL
RANGE
INTEGER
Settings
Unit
Step
-
-
Type
1
m%
1
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
xBase
0.01
-
-
%
0.001
Default
Description
0
Block of function
0
Analog input value
Description
Magnitude of deadband value
Range
Default
Description
unit
Base prefix (multiplication factor)
10
Cycl: Report interval (s), Db: In % of range,
Int Db: In %s
500
Zero point clamping in 0.001% of range
900.00
High High limit multiplied with the base prefix
(multiplication factor)
800.00
High limit multiplied with the base prefix
(multiplication factor)
-800.00
Low limit multiplied with the base prefix
(multiplication factor)
-900.00
Low Low limit multiplied with the base prefix
(multiplication factor)
-1000.00
Minimum value multiplied with the base prefix
(multiplication factor)
1000.00
Maximum value multiplied with the base
prefix (multiplication factor)
Dead band
Reporting type
5.000
Hysteresis value in % of range (common for
all limits)