1MRK 502 043-UUS B
14.8.6
14.9
14.9.1
14.9.2
14.9.3
Technical Manual

Technical data

Table 336:
DRPRDRE technical data
Function
Buffer capacity
Maximum number of analog inputs
Maximum number of binary inputs
Maximum number of disturbance reports
Maximum total recording time (3.4 s recording time and maximum number
of channels, typical value)
IEC 61850 generic communication I/O functions
SPGGIO
Identification
Function description
IEC 61850 generic communication I/O
functions
Functionality
IEC61850 generic communication I/O functions (SPGGIO) is used to send one single
logical signal to other systems or equipment in the substation.
Function block
SPGGIO
BLOCK
^IN
IEC09000237_en_1.vsd
IEC09000237 V1 EN
Figure 207:
SPGGIO function block
IEC 61850
IEC 60617
identification
identification
SPGGIO
-
Section 14
Monitoring
Value
40
96
100
340 seconds (100
recordings) at 50 Hz
280 seconds (80
recordings) at 60 Hz
ANSI/IEEE C37.2
device number
-
465