Monitored Data - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 12
Control
Table 194:
SESRSYN (25) Non group settings (basic)
Name
Values (Range)
GblBaseSelBus
1 - 6
GblBaseSelLine
1 - 6
SelPhaseBus1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseBus2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine1
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
SelPhaseLine2
Phase L1
Phase L2
Phase L3
Phase L1L2
Phase L2L3
Phase L3L1
Positive sequence
12.1.6
322
Unit
Step
-
1
-
1
-
-
-
-
-
-
-
-

Monitored data

Table 195:
SESRSYN (25) Monitored data
Name
Type
VDIFFME
REAL
FRDIFFME
REAL
PHDIFFME
REAL
Vbus
REAL
VLine
REAL
Default
Description
1
Selection of one of the Global Base Value
groups, Bus
1
Selection of one of the Global Base Value
groups, Line
Phase L1
Select phase for busbar1
Phase L1
Select phase for busbar2
Phase L1
Select phase for line1
Phase L1
Select phase for line2
Values (Range)
Unit
-
-
-
Hz
-
deg
-
kV
-
kV
1MRK 502 043-UUS B
Description
Calculated difference of
voltage in p.u of set voltage
base value
Calculated difference of
frequency
Calculated difference of
phase angle
Bus voltage
Line voltage
Technical Manual