Signals - ABB REG650 Technical Manual

Generator protection
Hide thumbs Also See for REG650:
Table of Contents

Advertisement

Section 8
Current protection
8.3.4
8.3.5
Table 81:
SDEPSDE (67N) Group settings (basic)
Name
Values (Range)
Operation
Disabled
Enabled
OpModeSel
3I0Cosfi
3I03V0Cosfi
3I0 and fi
DirMode
Forward
Reverse
Table continues on next page
196

Signals

Table 79:
SDEPSDE (67N) Input signals
Name
Type
I3P
GROUP
SIGNAL
V3P
GROUP
SIGNAL
BLOCK
BOOLEAN
BLKVN
BOOLEAN
Table 80:
SDEPSDE (67N) Output signals
Name
Type
TRIP
BOOLEAN
TRDIRIN
BOOLEAN
TRNDIN
BOOLEAN
TRVN
BOOLEAN
PICKUP
BOOLEAN
PUDIRIN
BOOLEAN
PUNDIN
BOOLEAN
PUVN
BOOLEAN
PUFW
BOOLEAN
PUREV
BOOLEAN
CND
INTEGER
VNREL
BOOLEAN
Settings
Unit
Step
-
-
-
-
-
-
Default
Description
-
Three phase group signal for current inputs
-
Three phase group signal for voltage inputs
0
Block of function
0
Blocks the non-directional voltage residual outputs
Description
Common trip signal
Trip of the directional residual overcurrent
Trip of non-directional residual overcurrent
Trip of non-directional residual overvoltage
General pickup signal
Pick up of the directional residual overcurrent function
Pick up of non directional residual overcurrent
Pick up of non directional residual overvoltage
Pick up of directional function for fault in forward
direction
Pick up of directional function for fault in reverse
direction
Direction of fault
Residual voltage release of operation of directional
modes
Default
Description
Disabled
Operation Disable / Enable
3I0Cosfi
Selection of operation mode for protection
Forward
Direction of operation forward or reverse
1MRK 502 043-UUS B
Technical Manual

Advertisement

Table of Contents
loading

Table of Contents